Question 1
Show windows and track lighting are covered in which NEC section?
Correct Answer:
NEC Section 220.46
Explanation:
The main concept is determining how to size the lighting load for a dwelling. NEC 220.46 provides the method for calculating the dwelling unit lighting load, and it includes common fixed lighting installations such as track lighting alongside other lighting fixtures. This is why it’s the best fit for showing how windows (as part of general lighting considerations) and track lighting are accounted for in load calculations. The other options cover different topics: 408 deals with panelboards and switches, 430 covers motors and motor circuits, and 230.71(B) relates to service equipment/ disconnecting means rather than how lighting loads are calculated. So, the section that specifically addresses calculating the lighting load for a dwelling unit is NEC 220.46.
Question 2
Where can you find the 25' tap rule?
Correct Answer:
NEC Section 240.21(B)(2)
Explanation:
The rule about a 25-foot tap length comes from the taps section of the NEC, specifically the provision that defines the allowable length for a tap conductor from the last overcurrent protective device to the point of utilization. This 25-foot limit is what lets a short, direct connection be treated under tap rules rather than as a full feeder, simplifying sizing and protection as long as other requirements are met. That exact 25-foot tap rule is found in NEC 240.21(B)(2). If the run is longer than 25 feet, different tap conditions apply (covered under other parts of 240.21(B)), not the 25-foot rule. The other options address unrelated topics: 230.6 concerns service disconnect requirements, and Table 430.250 deals with motor overload protection, not the tap-length rule. So the correct place to find the 25-foot tap rule is NEC 240.21(B)(2).
Question 3
General lighting loads for non-dwelling occupancies are detailed in which NEC resource?
Correct Answer:
NEC Table 220.42(A)
Explanation:
General lighting loads for non-dwelling occupancies come from NEC Table 220.42(A). This table lists the lighting unit load in VA per square foot for different types of nonresidential occupancies. To size feeders or a service, you multiply the building area by the unit load from the table for the specific occupancy, then apply any applicable demand factors and add to other loads as needed. The other sections referenced in the choices relate to different types of loads or parts of the code (such as motors or other calculations) and do not provide the general lighting unit loads for non-dwelling occupancies.
Question 4
A 30,000 VA load is supplied by a 240V single-phase feeder. What is the current in amps?
Correct Answer:
125.00 A
Explanation:
In a single-phase system, apparent power S equals voltage times current: S = V × I. So the current is I = S / V. Here, S is 30,000 VA and V is 240 V, so I = 30,000 / 240 = 125 A. Verifying: 125 A × 240 V = 30,000 VA, which matches the given load. If you were using real power instead of apparent power, you’d divide by the voltage and multiply by the power factor, but with apparent power the division by voltage gives the current directly.
Question 5
In feeder sizing, which type of load must be increased by 125%?
Correct Answer:
Continuous
Explanation:
The concept tested is how continuous loads are treated when sizing feeders. Continuous loads are defined as those that run for 3 hours or more in a 24-hour period. To prevent overheating and provide adequate margin for long-term operation, the ampacity for continuous loads is increased by 125% when sizing feeders and services. Noncontinuous loads do not get this increase because they aren’t sustained long enough to cause the same heating risk. In practice, you size the feeder by adding 1.25 times the continuous-load amperage to the actual amperage of the noncontinuous loads. For example, if there is a continuous load of 40 A and a noncontinuous load of 20 A, the feeder would be sized for 1.25 × 40 + 20 = 50 + 20 = 70 A. So the type that must be increased by 125% is the continuous load.
Question 1
Exam overview

About this Exam

Prepare with the NCCER Load Calculations – Feeders and Services (26401-23) Practice Test practice quiz. This question bank includes 10 questions covering section, load, lighting, single-phase, and feeder. Use it to review important concepts, identify knowledge gaps, and build confidence for the related exam, course, or assessment.

More details

Additional Information

NCCER Load Calculations – Feeders and Services (26401-23) Practice Test

This practice set contains 10 questions from the matching question bank and focuses on section, load, lighting, single-phase, and feeder. Work through each question carefully, review the provided solutions, and revisit topics that need more study before your next attempt.

This is an independent study resource intended for practice and review; it is not an official examination or an endorsement by any organization named in the title.

Quiz information

Frequently Asked Questions

The complete question count is available after full access is unlocked.
No fixed duration is currently configured for this quiz.
Question explanations are included where they are available in the quiz content, helping you review the reasoning after answering.
Yes. You can retake the practice test again as you continue studying during your available access period.
After your access is confirmed, you can continue into the complete practice exam from this quiz flow.
Unless explicitly stated otherwise, this page provides independent practice material for study and exam preparation and is not the official examination itself.
Keep studying

Related Questions