Question 1
To assure proper calibration, which method is NOT permitted for testing a smoke detector?
Correct Answer:
An aerosol spray or canned smoke
Explanation:
Testing smoke detectors must use approved, reliable methods that simulate real smoke in a controlled, repeatable way. Aerosol spray or canned smoke is not permitted for calibration because its particle size, concentration, and distribution can vary greatly and it may leave residues inside the sensing chamber. That can lead to inconsistent results, nuisance alarms, or sensor drift, and it may not be approved by manufacturers or standards. In contrast, a calibrated test instrument provides a known, traceable stimulus; manufacturer-approved test gas can emulate smoke with a defined concentration and properties; and a controlled lab test procedure follows standardized steps to ensure repeatable, accurate verification. So the aerosol spray or canned smoke method is the one to avoid for proper calibration.
Question 2
What is the purpose of tagging an uninstalled device during inspection?
Correct Answer:
To distinguish it from active devices and document its status
Explanation:
Tagging an uninstalled device during inspection is about clearly marking that device so it is distinguished from live, active devices and its status is documented. This keeps the installation queue and records accurate, prevents confusion about what is or isn’t part of the active system, and provides traceability for future installation or follow-up work. It also helps ensure safety and proper coordination, since everyone knows that device is not yet installed or tested. This tag is not meant to trigger tests, bypass the device, or enable immediate use, which is why those options don’t fit.
Question 3
Complete records of all signals received at a supervising station must be retained for at least how long?
Correct Answer:
1 year
Explanation:
Records kept at a supervising station must be kept for one year. This retention period ensures there is a complete, verifiable history of every signal received—alarms, supervisory, and trouble signals—so the monitoring facility can review events, verify responses, support investigations, and satisfy regulatory and auditing needs. Keeping a full log for a year provides enough time to resolve disputes, analyze performance, and confirm that proper procedures were followed. Six months often isn’t enough to cover longer investigation windows, while two or three years adds unnecessary storage burden for routine operations; one year strikes the right balance for standard monitoring activities.
Question 4
Which documents are included as part of the required information to be provided?
Correct Answer:
As built design and installation documents and equipment specifications
Explanation:
The essential idea is to provide a complete record of what was installed and how it was intended to operate. As-built design and installation documents capture the actual field conditions, including locations of devices, wiring routes, panel configurations, and any changes from the original plan. Equipment specifications list the exact models, ratings, and capabilities of every component used. Together, these documents give a precise, verifiable picture of the fire alarm system, which is critical for future maintenance, testing, troubleshooting, upgrades, and regulatory inspections. Warranty certificates, maintenance logs, and employee training records are useful in their own right, but they don’t supply the comprehensive detail about the installed design and components that the required information packet should include.
Question 5
Secondary power supplies are required to have sufficient power to operate the fire alarm system in a non alarm condition for how many hours and then be capable of operating all notification devices for a minimum of how many minutes?
Correct Answer:
24 hours and 5 minutes
Explanation:
Backup power duration and signaling requirements ensure the fire alarm system stays functional during a power outage. The secondary power supply must be sized to keep the system operating in non-alarm condition for 24 hours, so the control panel, detectors, and other non-alarm functions remain active even if utility power is out. After that standby period, it must be capable of operating all notification devices for at least 5 minutes, providing continuous audible and visual alerts to warn occupants and support evacuation until power is restored or the incident is resolved. This combination ensures reliable monitoring and effective warning during extended outages, aligning with standard fire alarm code expectations.
Question 1
Exam overview

About this Exam

Prepare with the FDNY COF for Fire Alarm Systems Inspection, Testing and Service Technician (S-98) Practice Exam practice quiz. This question bank includes 10 questions covering alarm, testing, documents, included, and information. Use it to review important concepts, identify knowledge gaps, and build confidence for the related exam, course, or assessment.

More details

Additional Information

FDNY COF for Fire Alarm Systems Inspection, Testing and Service Technician (S-98) Practice Exam

This practice set contains 10 questions from the matching question bank and focuses on alarm, testing, documents, included, and information. Work through each question carefully, review the provided solutions, and revisit topics that need more study before your next attempt.

This is an independent study resource intended for practice and review; it is not an official examination or an endorsement by any organization named in the title.

Quiz information

Frequently Asked Questions

The complete question count is available after full access is unlocked.
No fixed duration is currently configured for this quiz.
Question explanations are included where they are available in the quiz content, helping you review the reasoning after answering.
Yes. You can retake the practice test again as you continue studying during your available access period.
After your access is confirmed, you can continue into the complete practice exam from this quiz flow.
Unless explicitly stated otherwise, this page provides independent practice material for study and exam preparation and is not the official examination itself.
Keep studying

Related Questions