NICET Level 3 Water Based Layout Exam 36 Questions And Answers Set 01
NICET Level 3 Water Based Layout Exam 36 Questions And Answers Set 01
EXAMS AND CERTIFICATIONS
36 Terms
|
NICET Level 3 Water Based Layout Exam 36 Questions And Answers Set 01
1 / 10
Terms in this set
36
What three pieces of information is a property owner required by NFPA to give to contractors?
Intended use of building, preliminary plan of building, knowledge of water supply
What force must a sway brace assembly be designed to withstand?
All tension and compression forces
What is the maximum pressure allowed on a standpipe system?
175 psi
What is a limitation of a Gantt chart?
A Gantt chart can misrepresent the relative size of work elements/activities
Which type of standpipe is required for a building with the highest floor at 45 feet above fire department access?
Wet automatic
What is the minimum size of the heat circulating pipes required for a 100,000 gallon elevated steel tank in -30°F?
3-inch
What is the correct course of action for relocating upright sprinklers to the pendant position?
Replace 3/4-inch pipe with 1-inch; use 1/2-inch nipples no longer than 4 inches
What is the correct hazard occupancy for a library with a large stack room area?
Ordinary hazard Group 2
What type of sprinkler is accepted for use in a combustible concealed space supplied by CPVC?
A UL listed sprinkler for the specific application
At what distance must a backflow preventer assembly be installed from a fire pump suction flange?
Not less than 50 feet, but not more than 60 feet
Unlock remaining 26 terms for $39.99