NICET Level 1 Water Based Layout Exam 141 Questions And Answers Set 02

EXAMS AND CERTIFICATIONS 141 Terms | NICET Level 1 Water Based Layout Exam 141 Questions And Answers Set 02
1 / 10
Terms in this set 141
The document that provides the designer with information about the intended use of the building
Owner's certificate NFPA 13-4.2
A K-8.0 sprinkler has _________ of the nominal discharge of a K-5.6 sprinkler
140% NFPA 13- Table 7.2.2.1
Where the design is based on the density/area method, the design area shall be a rectangular area having a dimension parallel to the branch lines at least _____ times the square root of the sprinkler operation.
1.2 NFPA 13-28.2.4.2.1
An intermediate level between the floor and ceiling of a level would be considered a ____
Mezzanine IBC-Section 202 Definitions
Which of the following shall be included with water supply capacity information
Flow location, residual pressure. NFPA 13-4.5.1
What NFPA standard refers to the Standard for the Installation of Standpipe and Hose Systems
14 NFPA 13-ch.2
The stock of a spare sprinklers for a protection facility having 400 sprinklers shall be no less than ____
12 NFPA 13-16.2.7.5
What type of pipe or tubing would have the least amount of friction loss
Plastic NFPA 13-Table 28.2.4.8.1
What class of standpipe is intended for use by trained personnel
Class II NFPA 14-3.3.22.2
All of the following materials shall be classified as group C except_____
Polystyrene
Melamine
Fluoroplastics
Phenolic
Polystyrene NFPA 13-20.4.7