A publicly accessible alarm box that can also be operated by one or more remote initiating devices or an auxiliary alarm system used to send and alarm to the communications center.
Master Alarm Box
These contain the name of protected premises, name of installer, location of protected premises, device legend and date of issue.
Shop drawings
Which kind of circuit doesn't include a redundant path?
Class B
If a deficiency is not corrected at the conclusion of system inspection, testing, or maintenance, the system owner or owner's designated representative shall be informed of the impairment in within how long?
24 hours and in writing
Air Sampling piping and sampling ports shall be inspected how often?
Semiannually
Who should be notified prior to initial acceptance testing?
Authority Having Jurisdiction
What is the minimum number of detectors that should be tested annually?
Two per circuit
Pressure Supervisory Signal-Initiating devices will initiate an off-normal signal at what pressure differential?
increase/ decrease of 10 psi (70kPa)
Where should a sound measurement be taken for sleeping areas?
At the pillow level in the area required to be served by the system using the A-weighted scale (dBA).
A lobby smoke detector shall be located on the ceiling within how far of the center line of each elevator door?
21 feet